PowerSafeEngineering
Home/Sample Report

Redacted sample · free PDF · no email required

Sample Arc Flash Study Report

A redacted excerpt built on the same template as our sealed studies. The tables are real model output from completed projects, with every client and equipment identifier removed. Read it here or download the PDF.

What’s inside an arc flash study report

Every report follows the same structure, whether the site is a hospital, a water reclamation plant or a distribution center. Here is what each section is for.

  1. 1

    Executive summary

    One to two pages: scope, where the data came from, and the headline result of each study — maximum fault current, under-rated equipment, coordination problems, incident-energy range and the number of DANGER locations.

  2. 2

    System overview, methods & assumptions

    A narrative of your distribution system, the software and modules used (SKM Power*Tools), and every assumption written out — utility data margin, cable lengths, inaccessible devices — so an auditor or the next engineer can follow the model.

  3. 3

    Short circuit & equipment evaluation

    Available fault current at every bus for each operating scenario, checked against each device's interrupting rating and each assembly's SCCR (NEC 110.9 / 110.10). Under-rated equipment is listed with a specific fix.

  4. 4

    Protective device coordination

    Time-current curves from the utility fuse down, existing vs. proposed settings tables your electricians can dial in directly, and a narrative of each coordination finding.

  5. 5

    Arc flash hazard analysis

    IEEE 1584-2018 incident energy, arc flash boundary and working distance for every location, the controlling scenario, sample WARNING / DANGER labels, and NFPA 70E PPE guidance.

  6. 6

    Recommendations & mitigation

    What to change and in what order — settings, replacements, maintenance switches, de-energized work rules — tied back to the finding that drives each one.

  7. A

    Appendices

    Field-verified one-line with fault current at each bus, utility correspondence, photographs, and the full SKM input/output reports. Load flow, voltage drop and motor starting sections are added when they are in scope.

A bound, PE-sealed PowerSafe arc flash study report with a printed NFPA 70E warning label

Sealed report, bound and digital

Sealed by the PE licensed in your facility’s state. The study date is the first thing an auditor looks for.

A sample time-current coordination curve showing an MCC main and branch breakers plotted against the upstream switchgear breaker, with proposed settings

Time-current curves & proposed settings

Coordination drives clearing time, and clearing time drives incident energy. Proposed settings come as a table your electricians can dial in.

Sample incident energy table (IEEE 1584-2018)

One row per location. These twelve rows are real SKM Power*Tools output from completed PowerSafe studies, with the tags renamed. Your electricians and EHS team work from this table, and it’s the data printed on each label.

LocationVoltageBolted / arcingIncident energyAF boundaryWorking dist. · box (in)Label
MSB (main line side)0.480 kV34.80 / 24.78 kA91.00 cal/cm²270 in18 in · 30×66×17DANGER
Fire pump controller0.480 kV17.24 / 13.28 kA44.65 cal/cm²173 in18 in · 72×66×18DANGER
FD-2 (line side)0.480 kV18.01 / 12.14 kA35.75 cal/cm²151 in18 in · 28×70×15WARNING
P-1 disconnect0.480 kV10.96 / 8.40 kA14.61 cal/cm²86 in18 in · 28×50×10WARNING
SWBD-1 (main line side)0.480 kV51.64 / 27.96 kA13.57 cal/cm²82 in18 in · 36×30×36WARNING
MCC-2 (line side)0.480 kV19.41 / 13.06 kA9.66 cal/cm²66 in18 in · 18×40×15WARNING
MCC-10.480 kV51.75 / 31.93 kA4.04 cal/cm²38 in18 in · 20×20×20WARNING
RP-10.208 kV1.62 / 0.63 kA2.12 cal/cm²26 in18 in · 20×44×6.5WARNING
HP-10.480 kV40.60 / 27.66 kA1.00 cal/cm²16 in18 in · 20×36×6WARNING
LP-10.208 kV6.79 / 3.01 kA0.34 cal/cm²8 in18 in · 20×36×6WARNING
P-1 VFD0.480 kV18.09 / 13.92 kA0.32 cal/cm²8 in18 in · 12×14×10WARNING
DP-10.480 kV5.08 / 3.76 kA0.09 cal/cm²4 in18 in · 32×91×12WARNING

The two DANGER rows sit upstream of every customer-owned device, so only the utility’s primary fuse can clear them and the arc runs to the 2-second limit. The report’s answer is a de-energized work rule, because no amount of PPE fixes that.

Bolted / arcing kA

Bolted fault current is the theoretical maximum. Arcing current is lower, and it is what actually determines how fast the protective device clears the arc.

Incident energy (cal/cm²)

Heat energy at the worker's face and chest at the working distance. It sets the minimum arc rating of the clothing. Above 40 cal/cm², we recommend de-energizing.

Arc flash boundary

The distance at which incident energy falls to 1.2 cal/cm², the onset of a second-degree burn. Anyone inside it needs arc-rated PPE.

Working distance · box size

IEEE 1584-2018 corrects the result for enclosure size and the electrode configuration (VCB, VCBB, HCB, VOA, HOA), which is why we measure the gear and don't assume it.

DANGER vs WARNING

DANGER means more than 40 cal/cm², where no energized work is permitted. In real studies, that location is usually the service line side, which only the utility's fuse can clear.

What our arc flash studies typically find

These patterns come from our completed reports. They are why a label table alone, with no coordination or equipment evaluation behind it, misses most of the value.

The worst hazard is usually upstream of everything you own

When a facility has a DANGER (>40 cal/cm²) location, it is almost always the service-entrance line side or a fire pump controller fed straight from the utility transformer. Only the utility's primary fuse can clear it, so the arc runs to the 2-second limit. The answer is a de-energized work rule there, not heavier PPE.

Under-rated equipment turns up in about half our studies

Typically 14 kA or 18 kA panel breakers seeing 22–36 kA of available fault current after a utility upgrade or a larger transformer. We check for a tested series rating first (NEC 240.86) before anyone recommends replacing gear.

Breakers left at factory default settings

Electronic-trip breakers are routinely found at their out-of-box settings, so they neither coordinate nor limit incident energy. A settings table is often the cheapest hazard reduction in the whole report.

Generator power raises incident energy

On generator, arcing current can fall below short-time and instantaneous pickups, so clearing slows down and incident energy climbs. We model both sources, report the worse case, and recommend dual settings groups or a maintenance switch where it matters.

An NFPA 70E arc flash warning label applied to medium-voltage switchgear in service

Labels installed on your equipment

Printed on a substrate suited to the environment and placed where a worker will actually read it. We don’t ship them in an envelope for you to sort out. Labels are valid only once the proposed settings are implemented, and the report says so.

⚠ WARNING
Arc Flash and Shock Hazard
Appropriate PPE Required
Incident energy9.66 cal/cm²
Working distance18 in
Arc flash boundary66 in
Min. arc rating9.66 cal/cm²
Shock hazard480 V AC
Limited approach42 in
Restricted approach12 in
Equipment: MCC-2 · Study date 04/2026
PowerSafe Engineering, LLC

The label itself

Every field NFPA 70E 130.5(H) requires, plus the study date. Print-ready files are included so you can replace damaged labels yourself.

Where these reports come from

39 PowerSafe projects since 2022, across Georgia and the Southeast. Client names are confidential. The mix by sector:

16

Water & wastewater utilities

Treatment plants, reclamation facilities, wells, pump stations, elevated tanks

9

Industrial & manufacturing

Food and poultry processing, packaging, beverage, equipment manufacturing

12

Commercial, institutional & distribution

Distribution centers, retail redevelopment, offices, churches, camps, port facility

2

Healthcare

Critical-access hospital; healthcare central utility plant

See the engineering in detail: case studies water & wastewater studies

What do you need the report for?

My facility needs a study

You need a first study, or your current one is over five years old or predates a system change. Get a written fixed-fee scope.

I’m specifying or subcontracting one

You’re a contractor, MEP firm or design engineer with a study section in the specs. We work as your study subconsultant.

I have a study. Is it still valid?

Send the date, the standard it cites (IEEE 1584-2002 or 2018), and any changes since. A PE will tell you whether it needs an update or a full redo.

Need a complete report for your sector?

The PDF is an excerpt. If you’re writing an RFP or comparing vendors, tell us your facility type and we’ll send a complete redacted study from a similar facility, with all the curves, settings sheets and appendices.

Or call (571) 310-6945

Just want the excerpt? Download the PDF. No form required.

No obligation — you don’t need drawings to start. Your information is never shared.

Sample report FAQ

Related: arc flash study services, label requirements, and how to prepare for a study.

At minimum: the system model's assumptions and data sources, a short circuit analysis with equipment duty evaluation, the protective device coordination that produces clearing times, incident energy and arc flash boundary for every location per IEEE 1584-2018, label data that meets NFPA 70E 130.5(H), and recommendations. If a report only has a label table, the clearing times behind it were never checked.

Find out where your facility stands.

A 10-minute call with a licensed PE — we'll tell you what your study should cover and what it should cost. No obligation.

Call (571) 310-6945Free Consultation